详细说明:Omron G3JA软启动器手册(英文版)pdf,Omron G3JA软启动器手册(英文版)omRon
Ordering Information
■ List of mode|s
Soft Starters(Complies with IEC 60947-4-2)
100 to 240-VAC Models
Rated operating
KW
HP
Model
Current of main Circuit
Current Adjustable 200 VAC 230 VAC 380/400/200 VAC 230 VAC 460 VAC
rating range(A) 50/60 Hz 50 Hz 415 VAC 60Hz60 Hz60 Hz
(A)
50 Hz
1 to 3
02to040.55
1.1
0.5
0505t015G3AD403BAC100240
3 to 9
055to1522
4075120.751215G3AD409BAC100240
16
5.3to16
1.1to2.2
7.5
1.5to31.5to55to10G3JAD416BAC100-240
6.7t0201.5t3755
7.
2t521055t010G3AD420BAC100240
2592127722to5555
3o75|310757.5to15G3AD425BAC100240
109to32937t7.57.5
15
3to10|5to107.5to20c3AD432BAc100240
173to51.955to11
5to1575to1515t30G3AD451BAC100-240
64
213to6455o15185
3075to207.5t20|20to40G3AD464BAC100-240
Note: The applicable motor capacities given in the table are reference values. Select a model so that the full load current of the motor is within the
adjustable range of the rated operating current of the main circuit of the G3JA Only motors that support star-delta starting, such as 3-phase
6-wire/12-wire motors, can be used
24-VDC Models
Rated Operating
kW
HP
Model
Current of main circuit
Current Adjustable 200 VAC 230 VAC 380/400/200 VAC 230 VAC460 VAC
rating range(A) 50/60 Hz 50 Hz 415 VAC 60 Hz 60 Hz60 Hz
A
50 Hz
1 to 3
02to0.40.55
1.1
0.5
050.5t015G3JAD403BAC/DC24
3 to 9
055to1.52
0.75 to 20.75 to 21.5 to 5G3JA-D409B AC/DC24
16
53to161.1to22
7.51.5 to 1.5 to 5 5 to 10 G3JA-D416B AC/DC24
7to201.5t375.5
7.52 to 5 2 to 5 5 to 10 G3JA-D420B AC/DC24
25
92to27722to5.5
5.5
11
3 to 7.53 to 7.57.5 to 15 G3JA-D425B AC/DC24
32
109to32937to757.5
15
3 to 10 5 to 107.5 to 20G3JA-D432B AC/DC24
173t5195.5to11
5 to 15 7.5 to 15 15 to 30 G3JA-D451B AC/DC24
64213t645510151853075102075t02020040G4AD464BACC24
Note: The applicable motor capacities given in the table are reference values. Select a model so that the full load current of the motor is within the
djustable range of the rated operating current of the main circuit of the G3JA Only motors that support star-delta starting, such as 3-phase,
6-wire/12-wire motors can be used
Accessories (Order Separately
Product name
Model
Remarks
Auxiliary Contact Blocks G32J-CA10
Contact configuration: 1 NO
G 32J-CA20
Contact configuration: 2 NO
G32J-CA0 1
Contact configuration: 1 NC
G32J-CA11
Contact configuration: 1 NO/1 NC
Fan
G32J-CF64
Round Terminal Block G32J-TA10
Set of 2 Adapters
Adapters
Note: Refer to page 24 for details.
Three-Phase Hybrid Soft Starter(Current Limit Start for 3-phase, 6-lead Motors G3JA-D
OmROn
Specifications
Ratings and characteristics
Ratings
Model G3JA
G3JA
G3JA
G 3JA
G 3JA-D425
G3JA
G3JA-D451 G3JA
D403
D409
D416
D420
D432
D464
Rated operating current
3A
9A
16A
20A
25A
32A
51A
64A
Heat dissipation, continuous 7W
7 W
7 W
8 W
8 W
OW14W
9 W
Rated operating voltage of main 200 to 480 VAC, 50/60 Hz, 3-phase(=10%)
circuit
Main circuit power Wire gauge 2.5 to 25 mm?(14 to 4 AWG)
supply terminals Tightening 12.3 to 3.4 Nm
(L1, L2, and L3)
torque
Main circuit load Wire gauge 2.5 to 16 mm2(14 to 6 AW G)
power terminals
Tightening 2. 3 to 3.4N-m
(T1, T2, and T3)
torque
Control terminals Wire gauge.2 to 2.5 mm2(24 to 14 AWG)
Tightening 0.5 to 0.9 Nm
torque
Rated operating current
3A
9A
16A
20A
25A
32A
51A
64A
Maximum delta current
1.74A
5.2A
9.3A
11.6A
14.5A
174A
29.6A
36.5A
Overload current range
1103A3to9A53016A67t020A92t027A109t0329A173519A2131064A
Control voltage
100 to 240 VAC or 24 VAC, 50/60 Hz. 24VDC
Short Circuit Coordination Maximum Fuse or Circuit Breaker Size) Type 1
Item
ModelG3JA
G3JA
G3JA
3JA-
G3JA
G3JA-
G3JA
G3JA-
D403
D409
D416
D420
D425
D432
D451
D464
UL Class K5 and rK5 fuses
Rated breaking current: 5 kA
Rated breaking current: 10 kA
UL listing(600 v)
10A
0A80A
100A
125A
200A
250A
UL-listed thermal
Rated breaking current 5 kA
Rated breaking current: 10 kA
electromagnetic circuit breaker 15 A 35 A 60A 80A
00A
125A
200A
250A
UL listing(600 v)
Main circuit
Item
Classification
CULus (UL 508)
IEC(EN/EC 60947-4-2)
Rated operating voltage
200 to 480 VAC
400VAC
Isolation rated voltage
600 VAC
500 VAC
Dielectric strength( between control 2,200 VAC
2.500VAC
and main circuits)
Repetitive peak voltage
1,400V
1400V
Operating frequency
50/60Hz
Utilization category
Intermittent duty
AC-53b
Single-phase/3-phase
Equipment designed for 3-phase only
Rated impulse voltage
6 kV
DV/DT protection
1,000Vus
Overvoltage category
Environmental conditions
Classification
CULus(UL 508)
IEC(EN/IEC 60947-4-2)
Ambient operating temperature
0to50°C
Ambient storage temperature -25 to 85C
Elevation
2 000 m max
Humidity
5% to 85%(with no condensation)
Pollution degree
Degree of protection
P20
4 Three-Phase Hybrid Soft Starter(Current Limit Start for 3-phase, 6-lead Motors) G3JA-D
omRon
Control circuit
Item
Classification cULus(UL 508)
IEC(EN/IEC 60947-4-2)
Rated operational voltage
100 to 240 VAC 50/60 Hz. 24 VAC 50/60 Hz. 24 VDC
Voltage range
±10% of control voltage
Overvoltage cate gory
IIll (See note
Input onstate voltage minimum during 90 VAC max (100 to 240 VAC), 15.2 VAC/21.6 VDC max (24 VAC/DC)
start(A1, A2)
Input offstate voltage maximum(Al, A2) 30 VAC min (100 to 240 VAC). 12 VAC/17 VDC min(24 VAC/DC)
offstate current consumption 2 mA max.
Onstate current consumptian, with Fan 195 mA max at 120 VAC/140 mA max at 240 VAC, 650 mA max at 24 VAC/790 mA max at 24 VDC
(A2)
Onstate current consumption, without 185 mA max at 120 VAC/125 mA max at 240 VAC, 570 mA max at 24 VAC/695 mA max at 24 VDC
Fan(A2)
Note: Overvoltage category l applies when control or auxiliary contacts are connected to an SELV or PELV circuit.
Auxiliary Contacts
item
Classification
CULUs (UL 508)
EC(ENEC6094742)
Rated operational voltage
250 VAC/30VDC
250 VAC/30VDC
Rated impulse voltage
4kV
Dielectric strength
, VAC
2.000VAC
Overvoltage category
Il(See note)
Operating frequency
50/60Hz
Utilization category
D300
AC15
B-97,-98
Contr。 I circuit
Electromagnetic relay
(overloadfault) configuration
Num ber of contacts
Contact
NO contact
Current specifications AC/DC
Rated operating current 0.6 A at 120 VAC, 0. 3 A at 240 VAC
Contact switching
Open :72 VA
capacity
Close: 432 VA
Note: Overvoltage category lI applies when control or auxiliary contacts are connected to an SELV or PELV circuit.
Standard functions
Item
Classification
cULus(UL508)
IEC(EN/EC 60947-4-2)
Start time
2s,5s,10s,or15s
Current limit
150%,250%6,300%, or 350% of full-load current
Weight
Approx 860 g
Vibration and shock Resistance
tem
Classification
cULus(UL 508)
IEC(EN/EC 60947-4-2)
Vibration
Destruction 25-m/s2 peak, 10 to 55 to 10 Hz, 0. 19-mm single amplitude
resistance
Malfunction
10-m/s- peak, 10 to 55 to 10 Hz, 0.075-mm single amplitude
Shock resistance Destruction 300 m/s2(30 G)
Malfunction
150m/s2(15G)
Three-Phase Hybrid Soft Starter(Current Limit Start for 3-phase, 6-lead Motors G3JA-D
OmROn
Other Specifications
item
Classification
CULUs (UL 508
IEC(EN/IEC 60947-4-2)
EMI(emission test) Noise terminal voltage -
class a
Radiation field
Class a
EMS
Electrostatic
4 kv contact discharge and 8 kv air discharge
(immunity test) discharge
Radio frequency
Conforms to lEC 60947-4-2
electromagnetic field
Electrical fast
Conforms to IEC 60947-4-2
transient
Surge im munit
Conforms to lEC 60947-4-2
■ Applicable Standards
Safety standards
UL 508 ( Listing: File No. E96956), CSA 22.2 No. 14, EN/EC 60947-4-2
EMC Directives
Emissions: EN 5501 1 Group 1 Class A
Immunity: EN 61000-4
6 Three-Phase Hybrid Soft Starter (Current Limit Start for 3-phase 6-lead Motors)G3JA-D
omRon
Connections
Wiring
TwO-wire Connections
Three-wire Connections
lEC
IEC
Transforme
Transfomer
GRD
1
Main
circuit
2-vrire
circu t
m(Motor
M Motor
Control te rmina
Control terminals
NEMA
NEMA
Main circuit(Motor
Main circuit Motor
terminals
Start
(See note 1.)
Overload/fault
Overload
Control term inals
Control terminals
Operation Chart: Two-wire Connections with Forward/
Operation Chart: Three-wire Connections with Main Circuit
Reverse rotation
Fault shutoff
Start
A1-A2
A1-A2
1-A2
Normal
0-speed
3-24i(See note 2)
Normal
23-241( ee note2)
3-24(See note 2)
Note: 1. Always keep terminal 1 open
2. Operation of the Auxiliary Contact Block
Three-Phase Hybrid Soft Starter(Current Limit Start for 3-phase, 6-lead Motors G3JA-D
OmROn
Examples: Main Circuit Fault Shutoff Forward/Reverse Rotation
Note: Provide a time lag of at least 1.0 s between forward and re
rotation
IEC
IEC
」
Tc W Transformer
Transformer
KM1F
KM2¥-
GRD
GRD
B2 E-
Moto
Main
SB3E.
circuit
-SA
terminals
- Km2
KM1-KM2
Overload/fault
Control terminals
Overload/fault
Control terminals
NEMA
NEMA
Main circuit (motor
R
Main circuit ( Motor
terminals L3
terminals L3
H3 H2
1H4 Transformer
GRD
TRansformer
STart
FOR 4 REV
R
F
A2+979
Overload/fault
Control terminals
Overload/fault
Control terminals
Note: Operation chart is same as for Three-wire Connections.
Note: Operation Chart is same as for Two-wire Connections
8 Three-Phase Hybrid Soft Starter(Current Limit Start for 3-phase, 6-lead Motors) G3JA-D
ORon
Operation
■ Operating Modes
Current Limit Start
Start Time for a current limit start
This start mode is used when the maximum current must be limited
a built-in current transtormer (CT)is used to detect the motor
at startup. During the start time, the thyristor will reduce the motor
current. The completion of motor startup is determined by detecting
terminal voltage to limit the current at startup. During stable
the convergence of the current as the speed of the motor increases
operation, the built-in bypass relay will be ON
The soft starter operation is then changed to stable operation. The
start time given here is a guideline for when the total load current set
The current limit can be set to 150%, 250% 300%, or 350% of the
on the overload FLa setting dial and the actual load current are the
Full-load current. The start time can be set to 2s.5s. 10s. or 15s
same. f the motor load is smaller the motor will start faster. so that
actual start time will be shorter than the start time given here
Direct input
Current limit start
when set to 350%6
of total load current
Start time
Stable
Description of Functions
Overload protection
Phase loss
The G3JA-D is equipped with overload protection The overload
The G3JA-D monitors phase loss. If phase loss lasts for two power
the rated full-load current of the motor through the overload FLg e5
class can be set to off10. 15. or 20. Either automatic or manua
supply frequency cycles, the G3JA-D turns OFF the output, indicates
mode can be used to reset an overload (trip). Set the trip current to
the phase loss with a flashing led indicator and closes the alarm
contact
setting dial. When an overload fault occurs, the G3JA-D indicates the
overload with a flashing LED indicator and closes the alarm contact.
Current Imbalance
Overtemperature
The G3JA-D monitors the phase current imbalance. If the imbalance
exceeds the preset limit, the G3JA-D turns OFF the output, indicates
The G3JA-D monitors SCR temperature through an internal
the current imbalance with a flashing led indicator and closes the
thermistor. If the SCR gets too hot, the G3JA-D turns OFF the
alarm con tact
output, indicates the overtemperature status with a flashing LED
indicator and closes the alarrn contact
Shorted scr
The G3JA-D always checks the SCR for a short circuit before the
starting sequence. If a short circuit is found, the G3JA-D stops the
tarting sequence, indicates the short circuit with a flashing LED
dicator and closes the alarm contact
Three-Phase Hybrid Soft Starter(Current Limit Start for 3-phase, 6-lead Motors G3JA-D
OmRon
Nomenclature
Part Names and Functions
Main Circuit Terminals
Power Supply Side
DIP Switch Confiquration
Use the dip switch to set the functions
DIP switch
Function
p
Current limit start setti
4
Reset Button
All faults can be reset by pressing the Reset Button or turring
Overload class selection
OFF the control power supply Cooling tirme may be required
6
before overload and overtemperature can be rese
OmRon
Overload reset
Note: Test Mode for overload testing will be entered when the
Reset Button is pressed for at least 1 second. Test Mode will
G3JA-D
Optional auxiliary relay #1
be canceled when the Reset Button is pressed again
SOFT STARTER
(Normal/Up-to-speed
Overload FLA Setting Dial
Use this dial to set the trip current to the rated
full-load current of the motor
PHASE IMEA_ANCE
HHCRF)
RUN/FAULT Indicator
RUN/FALLT
The G3A-D uses one indicator to indicate both
normal operation( RUN) and faults(FAULT). If the
G3JA-d detects a fault. it turns off the motor and
indicates the fault with a flashing LED indicator.
The G3JA-D monitors the following conditions
Control terminals
6a②
Fault
Flashing indicator status
The G3JA-D has five input terminals on the front
Overload
Each terminal is described in the following table
Terminal
Description
A1Control power supply/START input
emperature
STOP input
Phase I
A2Control power supply common
Current
97 NO auxiliary contact(auxiliary contact for fault detection outpu:) Main Circuit Terminals,
imbalance
98 NO auxiliay contact(auxiliary contact for tault detection outpu;
Load side
Shorted
SCR
Auxiliary Contacts
The G3JA-D is equipped with one auxiliary contact as
a standard feature. It is used for fault detection output.
An optional Auxiliary Contact Block can be added
and DIP switch pin number 8 can be used to set the
operating status to output (either Normal or Up-to
speed)
10 Three-Phase Hybrid Soft Starter(Current Limit Start for 3-phase, 6-lead Motors ) G3JA-D